40 CFR Part 60, Table 1
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
| Municipal waste combustor technology | Before April 28, 2009,nitrogen oxides emission limit(parts per million by volume) a | On and after April 28, 2009,nitrogen oxides emission limit(parts per million by volume) a |
|---|---|---|
| Mass burn waterwall | 205 | 205 |
| Mass burn rotary waterwall | 250 | 210 |
| Refuse-derived fuel combustor | 250 | 250 |
| Fluidized bed combustor | 180 | 180 |
| Mass burn refractory combustors | No limit | No limit. |
a Corrected to 7 percent oxygen, dry basis.
[71 FR 27334, May 10, 2006]